6. B modeling results#

6.1. Tested values#

6.1.1. Linear density of normal force on the vertical section of the concrete plate#

Node

Reference Value

Tolerance

\(\mathit{N1}\)

—9.99125765.104N/m

1.526%

\(\mathit{N3}\)

—9.99125765.104N/m

1.526%

6.1.2. Normal force in the cable#

Node

Reference Value

Tolerance

\(\mathit{N5}\)

1,99825153.105N

—0.001%

\(\mathit{N6}\)

1,99825153.105N

—0.193%

6.1.3. Normal force in the cable via the POST_RELEVE_T command#

Node

Reference Value

Calculated Value

\(\mathit{N5}\)

1,998224892.105N

1,9982248921222.105N

\(\mathit{N6}\)

1,994393252.105N

1,9943932520206.105N

6.2. notes#

The calculated values actually correspond to those theoretically expected. A state of compression is indeed obtained for the concrete plate.